Technicial Specifications
Standby Rating | 2500 kVA 2500 kVA |
Prime Power Rating | 2275 kVA 2275 kVA |
Emissions/Fuel Strategy | Low Fuel, Low Emissions Low Fuel, Low Emissions |
Voltage | 380 to 11000 Volts 380 to 11000 Volts |
Frequency | 50 Hz 50 Hz |
Speed | 1500 rpm 1500 rpm |
Duty Cycle | Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime, Continuous |
Maximum Rating | 2500 kVA 2500 kVA |
Minimum Rating | 2000 kVA 2000 kVA |
Engine Model | 3516B TA, V-16, 4-Stroke Water-Cooled Diesel 3516B TA, V-16, 4-Stroke Water-Cooled Diesel |
Bore | 6.69 in 170 mm |
Stroke | 8.46 in 215 mm |
Displacement | 4764.73 in 78.08 l |
Compression Ratio | 15.5:1 15.5:1 |
Aspiration | TA TA |
Fuel System | Electronic unit injection Electronic unit injection |
Governor Type | Adem™3 Adem™3 |
Length - Minimum | 233.4 in 5928 mm |
Length - Maximum | 251.7 in 6377 mm |
Width - Maximum | 90 in 2286 mm |
Height - Maximum | 93.2 in 2367 mm |
Dry Weight - Genset (minimum) | 31900 lb 14470 kg |
Dry Weight - Genset (maximum) | 40320 lb 18290 kg |
Advantages and Features
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
Cat ECS Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirements
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 50�C (122�F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- IBC seismic certification
- EU Declaration of Conformity
- EU Declaration of Incorporation
- Eurasian Conformity (EAC)
Single-Source Supplier
- Components used in the generator set are selected at the design stage to provide optimum package performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment
-
Air Inlet
- Air cleaner
-
Cooling
- Package mounted radiator
-
Exhaust
- Exhaust flange outlet
-
Fuel
- Secondary fuel filters
- Fuel priming pump
- Primary fuel filter with integral water separator
-
Generator
- Matched to the performance and output characteristics of Cat engines
- IP23 Protection
-
Power Termination
- Busbar
-
Control Panel
- Cat ECS 100
-
General
- Paint - Caterpillar yellow except rails and radiators gloss black
Optional Equipment
-
Exhaust
- Exhaust mufflers (except Tier 4)
-
Generator
- Permanent magnet excitation (PMG)
- Internal excitation (IE)
- Anti-condensation heater
- Oversize and premium generators
-
Power Termination
- Circuit breakers, UL listed
- Circuit breakers, IEC compliant
-
Control Panels
- Generator temperature monitoring & protection
- Digital I/O module
- Load share module
- EMCP 4.4
- Remote monitoring software
-
Mounting
- Spring type vibration isolators
- IBC isolators
- Rubber anti-vibration mounts
-
Starting/Charging
- Oversize batteries
- Charging alternator
- Heavy duty starting system
- Jacket water heater
- Air starting motor with control and silencer
- Battery chargers
-
General
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- EU Certificate of Conformance (CE)
- The following options are based on regional and product configuration:
- Enclosures: Sound attenuated, weather protective
- Automatic transfer switches (ATS)
- UL 2200 package
- Integral & sub-base UL listed dual wall fuel tanks
- Integral & sub-base fuel tanks
- EEC Declaration of Conformity
- CSA Certification